HTS060D
| Performance Data, Refrigerant R404A | |||||||
| Evap Temp °C | -25°C | -20°C | -15°C | -10°C | -5°C | 0°C | +5°C |
| Duty kW | n/a | 16.78 | 21.90 | 27.60 | n/a | n/a | n/a |
| Current A | n/a | 24.12 | 24.12 | 24.12 | n/a | n/a | n/a |
| Power input kW | n/a | 12.62 | 12.62 | 12.62 | n/a | n/a | n/a |
| Dimensions: 1804mm Wide x 820mm Deep x 1921mm High (smaller case size available) | |||||||
| Model: HTS116D | R404A |
| Evaporating Temperature | -10°C
|
| Annual electricity consumption kWh/a | 47982 |
| Seasonal energy performance ratio SEPR | 3.51
|
| Data at full load ambient temperature 32°C | |
| Rated cooling capacity kW | 27.40 |
| Rated power input kW | 12.58 |
| Rated COP | 2.18 |
| Data at part load ambient temperature 25°C | |
| Cooling Capacity kW | 31.00 |
| Power input kW | 10.68 |
| COP | 2.90 |
| Data at part load ambient temperature 15°C | |
| Cooling Capacity kW | 34.00 |
| Power input kW | 9.54 |
| COP | 3.56 |
| Data at part load ambient temperature 5°C | |
| Cooling Capacity kW | 36.90 |
| Power input kW | 8.44 |
| COP | 4.37 |
| Data at ambient temperature 43°C | |
| Cooling Capacity kW | N/A
|
| Power input kW | N/A
|
| COP | N/A
|
| Degradation coefficient Cdc | 0.25
|
| Capacity control | Step |
| Product code |
HTS116D
|
|
Power Supply Requirement
|
3-phase |
|
Temperature
|
High |
|
Part Number
|
A9020-61D |
|
Refrigerant
|
HFC |
Together with our Service Partners, we offer a range of service plans to oversee, manage and monitor your installation.
Our spare parts and consumables are available in high quantities for at least 10 years after the purchase of your installation.
Hubbard has a broad range if transparent warranty policies, for our different products and customer groups.